TC Series DIN 48*48 Type                                                               
 

 


TC-48 Series
TC48-AN-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Timmer
Model:TC48-AN--
Alarm:Non
Display Method:Non
Display Tolerance:Non
Display Range:Non
Setting Method:Trimmer
Setting Tolerance:
1.0%
Setting Range:
100,200,400
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-48 Series
TC48-DD-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC48-DD--
Alarm:Non
Display Method:
0.36" 7-Segment Red Led
Display Tolerance:
0.5% of F.S.
Display Range:
-99 ~ +99 , 0 ~ 999
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-48 Series
TC48-DD---AH Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC48-DD---AH
Alarm:
AL+HB
Display Method:
0.36" 7-Segment Red Led
Display Tolerance:
0.5% of F.S.
Display Range:
-99 ~ +99 , 0 ~ 999
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-48 Series
TC48-DN-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC48-DN--
Alarm:Non
Display Method:Non
Display Tolerance:Non
Display Range:Non
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm